1. Application
HM1L series earth leakage circuit breaker is one of the new type earth leakage breakers which has been developed by the company using international advanced design and manufacturing technology. Suitable for a line of AC50/60Hz, rated voltage up to 400V, rated current 16A to 630A. and is acted as infrequently changeover of circuit or infrequent starting of motor.The breaker has overload, short-circuit and under-voltage protective function, which can protect the circuit and the power equipment against damage, meanwhile, it can provide protection to these fire risk that caused by these long-time existed grounding fault that can not be detected by the over-current protection.
This breaker can be installed vertically(upright) or horizontally(transverse).
The wiring of the breaker can not be in adverse direction, that means power supply line must be connected to terminal 1,3 and 5,and the load line connected to terminal 2,4 and 6.
The rated residual operating current I △ n and the maximum breaking time can be adjusted on site according to practical condition.
The leakage protection module still can work normally when the phase voltage reduced to 50V. It has the same overall size with the HM1 series breakers, which make the installation more exchangeable.
The breakers are suitable for isolation, its symbol are: —
The breakers comply with the demands of the following standards:
IEC60947-1 and GB/T 14048.1 General
IEC60947-2 and GB 14048.2 Low voltage breakers
IEC60947-4 and GB 14048.4 Contactors and motor starters
IEC60947-5.1 and GB 14048.5 Electrical equipments of electromechanical control circuit
Main Technical Specifications
1. Note: According to the pole number of product, it classifies three and four poles. The neutral pole (N-Pole) of the four-poles products has four types:
Type A: N-pole without over-current release unit, it has been connected all the time, not closing and opening with the other three poles.
Type B: N-pole without over-current release unit, which closing and opening with the other three poles.
Type C: N-pole fixed with over-current release unit, which closing and opening with the other three poles.
Type D: N-pole fixed with over-current release unit, it has been connected all the time, not closing and opening with the other three poles.
1. The limiting breaking and arc-over distance includes horizontal and vertical installation.
2. If the three-pole breaker of this series is connected with three phase load, the load can not have neutral line, otherwise the breaker will have fault action.
3. If the three-pole breaker of this series is connected with single phase load, the phase line will be connected to the left pole, and the neutral line is connected to the right pole, the middle pole is blanket
2. Protection Characteristic
3. Residual Current Operating Time of Earth Leakage Circuit Breaker
4.1 Non-delay type operation characteristics see table 4(l A n < 30mA should be Nondelay type)
Table 4
Note: ato IA n < 30mA earth leakage circuit breaker, 0.25A can instead of 5IA n According toa, adopt 0.25A, then 10 I A n is 0.5A.
4.2 Delay type operation characteristics see table 5
Limiting non-driven time of delay type earth leakage circuit breaker according to 2I